Tehnička podrška
Tehnička podrška
materijal
Mlin
pocinkovanog
nehrđajućeg čelika SS304
nehrđajućeg čelika SS316
Aluminij
FRP / GRP
završiti
G: Pre-pocinčani / PG / GI - za unutrašnju upotrebu na AS1397
H: Vruće pocinčane / HDG - za vanjsku upotrebu BS EN ISO 1461
S4: nehrđajući čelik SS304
S6: nehrđajući čelik SS316
P: Plastificirani - za unutrašnju upotrebu u JG / T3045
A: Aluminij u AS / NZS1866
FRP / GRP: Fiberglass ojačana plastika
F: na vatru da AS3013: 2005
Z cinkovana - za unutrašnju upotrebu BS EN 12329
E: elektrolitska sjajna - za nehrđajućeg čelika koriste
M: Mill / blaga / Plain Steel ISO 4995
Minimalna premaz debljine i mase na uzorcima koji nisu centrifugira (HDG) | ||||
Člana i to je T zahvat | Lokalni premaz debljine (Mi nimum)
μm |
Lokalni premaz Masa (minimalna)
g / m 2 |
Znači premaz debljine (minimalna)
μm |
Znači premaz Masa (minimalna)
g / m 2 |
čelik> 6 mm | 70 | 505 | 85 | 610 |
čelik> 3 mm do ≤ 6 mm | 55 | 395 | 70 | 505 |
čelik≥ 1,5 mm do ≤ 3 mm | 45 | 325 | 55 | 395 |
čelik< 1,5 mm | 35 | 250 | 45 | 325 |
inspekcija
Dimenzija Inspekcija
premaz debljine inspekcije
Nosač kablova Informacije o utovaru
Test opterećenja u skladu sa EN 61537: 2007
Q = UDL (ravnomjerno raspoređena opterećenja)
faktor sigurnosti = 1,7
L = srednji vijek
F = otklon = 1/100 srednjeg raspona (max.)
S = spoja lokacija
Navedena opterećenja primjenjuju na meki čelik proizvod samo .
Testiranje opterećenja Besca je u skladu sa EN 61537: 2001. U praktičnom smislu to pokriva kontinuirani / multi
span instalacije, ravnomjerno utovar duž, i cijelom širinom ležišta. Kraju raspona u
these installations should be reduced to 0.75 of the intermediate spans.
DEFLECTION: Besca’s load and deflection figures are in accordance with EN 61537:2007, with the characteristic
deflection of Unistrut Cable Tray limited to span/100 and load figures inclusive of a safety factor of 1.7.
ACCESSORIES: To ensure adequate support, accessories should be supported locally.
COUPLERS: The loading and deflection tables for Unistrut Cable Tray assume that the couplers are located at the
most onerous position within the span (i.e. mid span). To maintain the load/deflection figures stated in the tables,
the couplers should not be located in end spans or over support locations. Straight couplers were utilized for the
testing of the medium and heavy duty cable trays. Only one pair of couplers should be used per span.
Širina (mm) | Korisni Presjek (cm 2) | ||
lakšeg | Srednji | Težak zadatak | |
50 | 5.4 | 11.4 | - |
75 | 8.1 | 17.4 | 35.8 |
100 | 10.9 | 23.5 | 48.1 |
150 | 16.6 | 35.6 | 72.7 |
225 | 24.9 | 53.7 | 108.2 |
300 | 49.9 | 70.4 | 144.8 |
450 | 75.1 | 106.1 | 213.6 |
600 | 95.3 | 141.8 | 285.6 |
750 | 119.3 | 171.1 | 357.6 |
900 | 143.3 | 205.6 | 429.6 |